Advanced WP7-90-27-300 / US UNIT / US VOLTAGE !

Diese Auswahl steht nicht zur Verfügung

Temperaturbereich bis °C
Spannung
Heizleistung in kW
Kühlleistung in KW
Förderleistung (l/min)
Produktnummer: Used US 200445 only US
Produktinformationen "Advanced WP7-90-27-300 / US UNIT / US VOLTAGE !"

Advanced WP7-90-27-300 SN 200445

 

Temperature up to: 90 °C / 194 °F

Heating capacity: 27 kW

Cooling capacity: 300 kW

Circulating medium: Water up to 90°C

Flow rate: max. 230l/min

Max. pressure: max. 2,3 bar

Motor capacity: 0,75 kW

 

 

Voltage: USA

Stock location: Single USA

Serial Nuber : 200445

Typ : Used Unit

 

Hydraulic functional equipment

·        Cooling and filling controlled by solenoid valve
·        Configurable automatical filling via cooling water or separate connection (ex works cooling water inlet)
·        Flow measurement by differential pressure
·        Level monitoring by magnetic float switch
·        Automatic temperature-dependent system closing (not for 90°C)
·        Flow monitoring by recording surface temperature of heating rods and flow
·        Bypass between to and from process with reduced cross-section
·        Dirt trap in cooling water supply, filling connection and return line of circulating system
·        Continuous bypass of heat exchanger by 3-way-motorvalve (WP7-180/200)
·        System pressure monitoring by pressure transmitter in extension vessel (WP7-150/180/200)
·        Booster pump for filling (WP7-180/200, 150° optional)
·        Saftey temp. limiter (STB) in heating and to process line (WP7-200)
·        Manometer in to process line at backside of unit
·        Medium circuit insulated (WP7-150/180/200)

 

Functional equipment electrical

 

·        Smart Controller (7" touch display)
·        Heating control by solid-state-relay
·        Control cabinet IP54

General equipment

·        Expansion vessel, heater and piping made of stainless steel
·        Heating with Incolloy stainless steel tubular heaters
·        Dirt trap (medium): EN-GJL-250; GP240GH+N
·        Unit ready for connection and  mounted on castors, thereof 2 swivel castors with brakes

 Special equipment

·        Special voltage 440-480V +/-5% / 60Hz 3p

·        Pipe connection for filling WK3 with ball valve
·        Special setting in the unit: - for manual filling
·        Air inlet valve (Art.No.06653) in the manual filling line, after ball valve Overflow valve for WP7 between to and from process up to 150° discharge pressure: * 1,5 bar for units  with flow measunring: the total flow rate of the device will be displayed.  (overflow valve will be mounted before flow measuring)

 

Professional package:

·        Smart Controller plus

·        Prequency converter
·        Pressure transducer
·        If a fault-current circuit breaker (FI) is installed in the electrical supply line to the TCU, a FI "Type B" must be        used.
·        If the rated current of the FI is 30mA only one TCU can be operated at this FI
·        Alarm status Alarms and Warnings by potential-free contact on clamp on I/O-board incl. warning for delta T (pre- and return run) and return run temperature (- no charge)
·        Special connections for Medium, cooling water and filling

 

Die Abbildungen und Zeichnungen, Größen-, Gewichts-, Verbrauchs-, Leistungsangaben sowie chemischen und physikalischen Angaben sind stets annähernd.