WP4S-150-18-120 SN250344
IM150B
Temperature up to: 150 °C
Heating capacity: 18 kW
Cooling capacity: 120 kW
Maximum flow rate: 73 l/min
Maximum pressure: 7.5 bar
Functional equipment hydraulic:
- Bypass between to and from process with reduced crosssection
- Level monitoring by magnetic float switch
- Manometer in to process line at backside of unit
- Flow measurement by differential pressure
- Flow monitoring by recording flow
- Dirt trap in cooling water supply and return line of circulating system
- Medium circuit insulated
Functional equipment electrical:
- Smart Controller Plus (7" touch display)
- Heating controlled via SSR
- Control cabinet IP54 forced ventilation
General equipment:
- Expansion vessel, heater and piping made of stainless steel
- Heating with Incolloy stainless steel tubular heaters
- Dirt trap (medium): 1.4408
Selected features:
- Pressure gauge in pre run (M.PG1.WP4S)
- Professional package (PRO.WP4S)
consisting of:
Smart Controller plus, frequency converter and
pressure transducer
If a fault-current circuit breaker (FI) is
installed in the electrical supply line
to the TCU, a FI "Type B" must be used.
If the rated current of the FI is 30mA
only one TCU can be operated at this FI
- Tool drainage by compressed air (M.TDA.WP4S)
with non-return valve, solenoid valve, fitting
for compressed air, impulse via
control unit/ overflow to
cooling water + pressure release
Connection: Hose nipple 10 mm
- Current interface 20mA Arburg (SSC.IFARBURG)
via 9-pin D-sub connector
- Euromap 82.1 based on OPC UA, connection RJ45 (SSC.IFOPC)
- electrical preparation for SFC at TCU WP4S (SFC.R2.WP4S)
- plug 32 A/ CEE completely installed (E.PSC32.WP4S)
- Connection for external temperature sensor: PT 100 (SSC.EXTSPT3)
2-conductor or 3-conductor
The illustrations and drawings, size, weight, consumption, performance, chemical and physical data are always approximate.